A310 PT(automation)

FLIR A310 pt thermal cameras can be installed almost anywhere to monitor the condition of your critical equipment and other valuable assets. Designed to help safeguard your plant and measure temperature differences, they allow you to see problems before they become costly failures — preventing downtime and enhancing worker safety. FLIR A310 pt is ideal for various applications that require temperature measurement capabilities including: substation, transformer, waste bunker, and coal pile monitoring.

  • MULTI-SENSOR

    The FLIR A310 pt pan/tilt has all the necessary features and functions to build single- or multi-camera solutions. The FLIR A310 pt can pan +/- 360° continuous and tilt +/- 45°. It is ideal to cover large areas. Typical application examples are coal pile, waste bunker and substation monitoring, utilizing standard Ethernet hardware and software protocols. The FLIR A310 pt is a multi-sensor and includes a lowlight 36x zoom color CCD camera.

  • DESIGNED FOR USE IN HARSH ENVIRONMENTS FLIR SENSORS MANAGER

    A310 pt is an extremely rugged system that meets IP66 requirements, protecting the camera from dust and water Each FLIR A310 pt comes with a single sensor copy of FLIR Sensors Manager. This intuitive software allows users to manage and control the cameras in a TCP/IP network

SPECIFICATIONS
OVERVIEW
Accuracy
±4°C (±7.2°F) or ±4% of reading
Alarm Functions
6 automatic alarms on any selected measurement function, camera temperature
Automatic Heater
Clears window from ice. Switched on at +4°C (39°F). Switched off at +15°C (59°F).
Azimuth Range
Az velocity 360° continuous, 0.1 to 60°/sec max
Detector Type
Focal Plane Array (FPA), uncooled microbolometer
Elevation Range
El velocity ± 45°, 0.1 to 30°/sec. max
Field of view (FOV)
6° × 4.5°
Focal Length
76 mm (3.0 in.)
Housing material
Aluminum
IR Resolution
320 × 240 pixels
List of Contents
Cardboard box, Pan & tilt with infrared camera including lens, and visual camera, FLIR Sensors Manager download card, Lens cap, Printed documentation, Small accessories kit, User documentation CD-ROM
Object Temperature Range
–20 to +120°C (–4 to +248°F) 0 to +350°C (+32 to +662°F)
Packaging Size
671 x 564 x 464 mm (26.4 x 22.2 x 18.3 in.)
Size (L x W x H)
460 × 467 × 326 mm (18.1 × 18.4 × 12.8 in.)
Thermal Sensitivity/NETD
< 0.05°C @ +30°C (+86°F) / 50 mK
Weight
18.1 kg (40.0 lb.)
Zoom
1–8× continuous, digital, interpolating zooming on images
FLIR Screen-EST Mode
No
CONNECTIONS & COMMUNICATIONS
Ethernet
Control, result and image
Ethernet Communication
TBA
Ethernet Connector Type
RJ-45
Ethernet Protocols
Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP
Ethernet Standard
IEEE 802.3
Ethernet Type
100 Mbps
Ethernet Video Streaming
Two independent channels for each camera – MPEG-4, H.264, or M-JPEG
Video Out
Composite video output, PAL /NTSC compatible
ENVIRONMENTAL
Atmospheric transmission correction
Automatic, based on inputs for distance, atmospheric temperature and relative humidity
Bump
5 g, 11 ms (IEC 60068-2-27)
EMC
EN 61000-6-2 (Immunity), EN 61000-6-3 (Emission), FCC 47 CFR Part 15 Class B (Emission)
Emissivity Correction
Variable from 0.01 to 1.0
Encapsulation
IP 66 (IEC 60529)
Humidity (Operating and Storage)
IEC 60068-2-30/24 h 95% relative humidity +25° C to +40°C (+77°F to +104°F)
Operating Temperature Range
–25°C to +50°C (-13°F to +122°F)
Storage Temperature Range
–40°C to +70°C (–40°F to +158°F)
Vibration
2 g (IEC 60068-2-6)
IMAGING & OPTICAL
Array format
320 × 240
Color palettes
Color palettes (BW, BW inv, Iron, Rain)
Detector Pitch
25 µm
Detector Time Constant
Typical 12 ms
Effective Pixels
380.0
Electronic Zoom
12× continuous, digital, interpolating
f-number
1.3
Focal Plane Array (FPA)
1/4″ Exview HAD CCD
Focus
Automatic or manual (built in motor)
Image Frequency
30Hz
Lens Identification
Automatic
Minimum Focus Distance
4 m (13.11 ft.)
Optical Zoom
36× continuous
Spatial resolution (IFOV)
0.33 mrad
Spectral Range
7.5–13 µm
Video Standard
CVBS (ITU-R-BT.470 PAL), CVBS (SMPTE 170M NTSC)
MEASUREMENT & ANALYSIS
Area
10 boxes with max./min./average/position
External Optics & Windows Correction
Automatic, based on input of optics/window transmission and temperature
Isotherm
1 with above/below/interval
Measurement Corrections
Global and individual object parameters
Optics Transmission Correction
Automatic, based on signals from internal sensors
Programmable Presets
128.0
Reflected apparent temperature correction
Automatic, based on input of reflected temperature
Set-up Commands
Date/time, Temperature°C/°F
Spot Meter
10
POWER
Power
24 VAC (21-30 VAC; 24 VAC: 215 VA max. with heater) or 24 VDC (21-30 VDC; 24 VDC: 195 W max. with heater).